Cable Joints

Cable Straight Joint for 35 kV

Description
Premolded type cable straight joint for 35kV, which has a coincident structure with cable and has clover-leaf type inner shape for heat radiation
Features
Direct Burial Possible
Great Heat Radiation
Special Design for Smooth Distribution of Electrical Stress
Excellent Insulation Performance
Re-installable and Re-useable
Brand

Outline

Technical data

ITEM

15 PCJ

25 PCJ

35 PCJ

System Voltage

15 kV

25 kV

35 kV

Impulse Voltage ( BIL, 1.2 X 50§Á )

110 kV

240 kV

240 kV

Partial Discharge (Corona)

15.6 kV

25.8 kV

30 kV

15 min. Dry Withstand (D.C.)

65 kV

75 kV

125 kV

6 hr. Dry Withstand (A.C.)

36 kV

53 kV

69 kV

Applied standard

IEEE Std.404 (1993) IEEE Standard for Cable Joints for Use With Extruded Dielectric Cable Rated 5000-138,000 V and Cable Joints for Use With Laminated Dielectric Cable Rated 2500-500,000 V