ÇÏ´Ü javascipt ¿¡¼ ¼³Á¤
Distribution Line
SILICONE Dead-end Insulator for 35kV
Outline
Technical data
ITEM |
VALUE |
||||
Model No |
DN15SE-CT |
DN25SE-CT |
DN35SE-CT |
DN46SE-CT |
|
Voltage Class |
15 kV |
25 kV |
35 kV |
46 kV |
|
Number of Sheds |
4 |
6 |
8 |
11 |
|
Leakage Distance |
415 mm |
643 mm |
851 mm |
990 mm |
|
Dry Arcing Distance |
204 mm |
314 mm |
389 mm |
440 mm |
|
60 Hz Flashover |
DRY |
100 kV |
130 kV |
145 kV |
180 kV |
WET |
70 kV |
110 kV |
130 kV |
145 kV |
|
Impulse Flashover |
POSITIVE |
140 kV |
190 kV |
250 kV |
280 kV |
Radio Influence |
TEST |
10 kV |
20 kV |
25 kV |
25 kV |
AT 1000kHz |
10 §Å |
||||
Min.Specified Mechanical Load |
70(15,000) kN(lb) |
||||
Min.Torsional Load |
55(40) N-m(ft-lb) |
Applied standard
CEA LWIWG-01 (1996) Dead-end/suspension composite insulator for overhead
distribution line
IEC 1109 (1995-04) Composite insulator for a.c. overhead lines with a nominal voltage
greater than 1000V - Definition, test methods and acceptance criteria
ANSI C29.13-2000 American National Standard for Insulators - Composite - Distribution
Deadend Type
Not Breakable
Self-cleaning Function
Excellent Mechanical Characteristics
Hydrophobicity